1. Tabel konfigurasi unit kondensor pendingin
Dibandhingake karo panyimpenan kadhemen gedhe, syarat desain panyimpenan kadhemen cilik luwih gampang lan prasaja, lan cocog saka Unit punika relatif prasaja. Mulane, beban panas saka panyimpenan kadhemen cilik umum biasane ora perlu dirancang lan diwilang, lan unit condenser kulkas bisa dicocogake miturut taksiran empiris.
1,Freezer (-18~-15 ℃)Papan panyimpenan polyurethane baja warna kaping pindho (ketebalan 100mm utawa 120mm)
Volume / m³ | Unit kondensor | Evaporator |
10/18 | 3 HP | DD30 |
20/30 | 4 HP | DD40 |
40/50 | 5 hp | DD60 |
60/80 | 8 hp | DD80 |
90/100 | 10 HP | DD100 |
130/150 | 15 HP | DD160 |
200 | 20 HP | DD200 |
400 | 40 HP | DD410/DJ310 |
2.Chiller (2~5 ℃)Papan gudang baja poliuretan ganda sisi (100mm)
Volume / m³ | Unit kondensor | Evaporator |
10/18 | 3 HP | DD30/DL40 |
20/30 | 4 HP | DD40/DL55 |
40/50 | 5 hp | DD60/DL80 |
60/80 | 7 hp | DD80/DL105 |
90/150 | 10 HP | DD100/DL125 |
200 | 15 HP | DD160/DL210 |
400 | 25 HP | DD250/DL330 |
600 | 40 HP | DD410 |
Ora ketompo apa merek unit kompresor kulkas, ditemtokake miturut suhu penguapan lan volume kerja sing efektif saka panyimpenan kadhemen.
Kajaba iku, paramèter kayata suhu kondensasi, volume panyimpenan, lan frekuensi barang mlebu lan metu saka gudang uga kudu dirujuk.
Kita mung bisa ngira kapasitas cooling unit miturut rumus ing ngisor iki:
01), rumus kanggo ngitung kapasitas pendinginan panyimpenan kadhemen suhu dhuwur yaiku:
Kapasitas kulkas = volume panyimpenan kadhemen × 90 × 1,16 + simpangan positif;
Penyimpangan positif ditemtokake miturut suhu kondensasi barang sing beku utawa didinginkan, volume panyimpenan, lan frekuensi barang sing mlebu lan metu saka gudang, lan kisaran antara 100-400W.
02), rumus kanggo ngitung kapasitas pendinginan panyimpenan kadhemen aktif suhu medium yaiku:
Kapasitas refrigerasi = volume panyimpenan kadhemen × 95 × 1,16 + simpangan positif;
Kisaran panyimpangan positif antarane 200-600W;
03), rumus kanggo ngitung kapasitas pendinginan panyimpenan kadhemen aktif suhu rendah yaiku:
Kapasitas refrigerasi = volume panyimpenan kadhemen × 110 × 1,2 + simpangan positif;
Kisaran panyimpangan positif antara 300-800W.
- 2. pilihan cepet lan desain refrigeartion evaporator:
01), Evaporator kulkas kanggo freezer
Beban saben meter kubik diitung miturut W0=75W/m3;
- Yen V (volume panyimpenan kadhemen) < 30m3, panyimpenan kadhemen karo kaping mbukak Kerep, kayata panyimpenan daging seger, multiply koefisien A = 1.2;
- Yen 30m3
- Yen V≥100m3, panyimpenan kadhemen karo kaping mbukak Kerep, kayata panyimpenan daging seger, Multiply koefisien A=1.0;
- Yen kulkas siji, multiply koefisien B = 1,1; pilihan final saka penggemar cooling saka panyimpenan kadhemen W = A * B * W0 (W punika mbukak saka penggemar cooling);
- Cocog antarane unit kulkas lan pendingin udara saka panyimpenan kadhemen diitung miturut suhu penguapan -10 °C;
02), Evaporator kulkas kanggo panyimpenan kadhemen fronzon.
Beban saben meter kubik diitung miturut W0=70W/m3;
- Yen V (volume panyimpenan kadhemen) < 30m3, panyimpenan kadhemen karo kaping mbukak Kerep, kayata panyimpenan daging seger, multiply koefisien A = 1.2;
- Yen 30m3
- Yen V≥100m3, panyimpenan kadhemen karo kaping mbukak Kerep, kayata panyimpenan daging seger, Multiply koefisien A=1.0;
- Yen kulkas siji, multiply koefisien B=1.1;
- Kipas pendingin panyimpenan kadhemen pungkasan dipilih miturut W=A*B*W0 (W minangka beban kipas pendingin);
- Nalika panyimpenan kadhemen lan kabinèt suhu kurang nuduhake unit kulkasan, sing cocog karo unit lan cooler online bakal diwilang miturut suhu penguapan saka -35 ° C. Nalika panyimpenan kadhemen dipisahake saka kabinèt suhu kurang, sing cocog karo unit kulkas lan penggemar cooling saka panyimpenan kadhemen diitung miturut suhu penguapan -30 °C.
03), Evaporator kulkas kanggo kamar pangolahan panyimpenan kadhemen:
Beban saben meter kubik diitung miturut W0=110W/m3:
- Yen V (volume ruang pangolahan)<50m3, pingake koefisien A=1.1;
- Yen V≥50m3, pingake koefisien A=1.0;
- Kipas pendingin panyimpenan kadhemen pungkasan dipilih miturut W = A * W0 (W minangka beban kipas pendingin);
- Nalika kamar pangolahan lan kabinèt suhu medium nuduhake unit kulkas, pencocokan unit lan pendingin udara kudu diwilang miturut suhu penguapan -10 ℃. Nalika kamar pangolahan dipisahake saka kabinèt suhu medium, sing cocog karo unit panyimpenan kadhemen lan penggemar pendinginan kudu diwilang miturut suhu penguapan 0 °C.
Pitungan ing ndhuwur minangka nilai referensi, pitungan sing tepat adhedhasar tabel pitungan beban panyimpenan kadhemen.